CJ1W-CRM21

NJ/CJ-series CompoNet Master Units Increase the Range of Applicability of Sensors and Actuators.

Categories: , ,

Description

• Setup is simple. Make the master’s mode settings and set the baud rate, and you’re ready to go.

• Control up to 2,560 points and 384 nodes with one Master Unit.

• Intuitive memory mapping with separate areas for Word Slave Units and Bit Slave Units.

• Seven-segment display helps with startup and enables prompt detection of problems.

• Collect information from Slave Units using message communications, or use message communications to set parameters.

• Inherits the ease of use of the CompoBus/S.

• Flexible I/O allocations with software setting function.

 

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.
Name Appear-
ance
Specifications Number
of unit
numbers
allocated
Power
consumption (A)
Model Stand-
ards
Type of
communi-
cations
Maximum number
of I/O points per
Master Unit
5-V
system
24-V
system
CJ1
Special
I/O Unit
1779_lu_1_1 Remote I/O
communica-
tions
Message
communica-
tions
Word Slave Units:
1,024 inputs and 1,024
outputs (2,048 I/O
points total)
Bit Slave Units: 256
inputs and 256 outputs
(512 I/O points total)
1, 2, 4,
or 8
0.4 CJ1W-CRM21 CE, U,
U1, L,
N
Note: Observe the following precautions if you use the CompoNet Master Unit in an NJ-series Machine Automation
Controller.
• Supported only by the CPU Units with unit version 1.01 or later and the Sysmac Studio version 1.02 or higher.
• You cannot use the simple backup function.
• You cannot send FINS commands to the CompoNet Master Unit.

Software

How to Select Required Support Software for Your Controller

The required Support Software depends on the Controller to connect. Please check the following table when purchasing the Support Software.

Item Omron PLC System Omron Machine Automation Controller System
Controller CS, CJ, CP, and other series NJ-series
Software FA Integrated Tool Package CX-One Automation Software Sysmac Studio

FA Integrated Tool Package CX-One

Product
name
Specifications Model Stand-
ards
Number of
licenses
Media
FA
Integrated
Tool
Package
CX-One
Ver.4.[]
The CX-One is a comprehensive software package
that integrates Support Software for OMRON PLCs
and components.CX-One runs on the following OS.
OS:Windows XP (Service Pack 3 or higher, 32-bit
version)/Windows Vista (32-bit/64-bit version)/
Windows 7 (32-bit/64-bit version)/Windows 8 (32-bit/
64-bit version)/Windows 8.1 (32-bit/64-bit version)/
Windows 10 (32-bit/64-bit version)

CX-One Version 4.[] includes CX-Integrator Ver.3.[].
For details, refer to the CX-One catalog (Cat. No.
R134)

1 license
*1
DVD
*2
CXONE-AL01D-V4

*1. Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.
*2. The CX-One is also available on CD (CXONE-AL[][]C-V4).

Automation Software Sysmac Studio

Please purchase a DVD and required number of licenses the first time you purchase the Sysmac Studio. DVDs and licenses are available individually. Each model of licenses does not include any DVD.

Product
name
Specifications Model Stand-
ards
Number of
licenses
Media
Sysmac
Studio
Standard
Edition
Ver.1.[][]
The Sysmac Studio is the software that provides an
integrated environment for setting, programming,
debugging and maintenance of machine automation
controllers including the NJ/NX-series CPU Units,
NY-series Industrial PC, EtherCAT Slave, and the HMI.Sysmac Studio runs on the following OS.
OS: Windows 7 (32-bit/64-bit version)/Windows 8 (32-
bit/64-bit version)/Windows 8.1 (32-bit/64-bit version)/
Windows 10 (32-bit/64-bit version)

The Sysmac Studio Standard Edition DVD includes
Support Software to set up EtherNet/IP Units,
DeviceNet slaves, Serial Communications Units, and
Support Software for creating screens on HMIs (CX-
Designer).
Refer to your OMRON website for details.


(Media only)
DVD SYSMAC-SE200D
1 license
*
SYSMAC-SE201L

* Multi licenses are available for the Sysmac Studio (3, 10, 30, or 50 licenses).

 

Communication Specifications

Item Specification
Communications protocol CompoNet Network protocol
Types of communications Remote I/O communications (programless,constant sharing of data with Slave Units)and message
communications (explicit message communications as required with Slave Units and FINS message
communications as required with Controllers *1)
Baud rate 4 Mbps *2,3 Mbps,1.5 Mbps,93.75 kbps
Modulation Base-band
Coding Manchester code
Error control Manchester code rules,CRC
Communications media The following media can be used.*3
Round cable I (JIS C 3306,2-conductor 0.75 mm2)
Round cable II (JIS C3306 4-conductor 0.75 mm2)
Flat Cable I (DCA4-4F10 Standard Flat Cable)
Flat Cable II (DCA5-4F10 Sheathed Flat Cable)
Communications distance
and wiring
Refer to Cable Types,Baud Rates,and Maximum Distances.
Connectable Master Units CompoNet Master Units
Connectable Slave Units CompoNet Slave Units
Maximum I/O capacity Word Slave Units:1,024 inputs and 1,024 outputs (2,048 I/O points total)
Bit Slave Units:256 inputs and 256 outputs (512 I/O points total)
Maximum number of nodes Word Slave Units:64 input nodes and 64 output nodes
Bit Slave Units:128 input nodes and 128 output nodes
Repeater Units:64 nodes
Bits allocated per node
address
Word Slave Units:16 bits
Bit Slave Units:2 bits
Maximum number of nodes
per trunk line or sub-trunk
line
32 nodes (including Repeater Units)
Applicable node addresses Word Slave Units:IN0 to IN63 and OUT0 to OUT63
Bit Slave Units:IN0 to IN127 and OUT0 to OUT127
Repeater Units:0 to 63
Repeater Unit application
conditions
Up to 64 Repeater Units can be connected per network.When Repeater Units are connected in series
from the Master Unit,up to 2 extra segment layers can be created (i.e.,up to 2 Repeater Units are
allowed between a Slave Unit and the Master Unit).
Signal lines Two lines:BDH (communications data high)and BDL (communications data low)
Power lines Two lines:BS+and BS –(power for communications and internal Slave Unit circuits)
Power is supplied from the Master Unit or Repeater Units.
Communications power
supply
24 VDC ± 10%
Connection forms Flat Cable at baud rate of 93.75 kbps:No restrictions
Other cables or baud rates:Trunk line and branch lines
Connections for Slave Units and Repeater Units:T-branch or multidrop connections
*1. FINS message communications are supported by CJ-series Controllers only.
*2. Drop-line connections are not supported with a baud rate of 4 Mbps, so Slaves with prewired cables (Bit Slaves)
cannot be used.
*3. Round cable, Flat Cable, and Flat Cable II are all different types of cable. To use more than one type of cable at a
time, Repeater Units must be used to separate them on trunk lines and sub-trunk lines.

Cable Types, Baud Rates, and Maximum Distances

This section provides specifications on the maximum cable length and maximum number of nodes for each type of cable. Do not exceed these specifications.

CJ1W-CRM21 Specifications 3

Restrictions (at Baud Rate of 4 Mbps (No Branch Lines))

Cable type Maximum length per segment
(maximum length with
Repeater Units)
Branch
line
length
Total branch
line length
per segment
Branch
location
restrictions
Maximum number of
Slave Units per
segment *2
Round cable I 30 m (90 m) 0 m *1 0 m *1 32 nodes
Flat Cable I and Flat Cable II
Round Cable II
30 m (90 m) 0 m *1 0 m *1 32 nodes

*1. T-branches cannot be connected (only multidrop connections are possible).
*2. Number of nodes including Repeater Units

Restrictions (at Baud Rate of 3 Mbps)

Cable type Maximum length
per segment
(maximum
length with
Repeater Units)
Branch
line
length
Total
branch line
length per
segment
Branch
location
restrictions
Maximum
number of
nodes per
branch *1
Sub-
branch
line
length
Total sub-
branch line
length per
segment
Maximum
number
of Slave
Units per
segment *2
Round cable I 30 m (90 m) 0.5 m 8 m 3 branches/m 1 node 0 m 0 m 32 nodes
Flat Cable I
and Flat Cable II
Round Cable II
30 m (90 m) 0.5 m 8 m 3 branches/m 1 node 0 m 0 m 32 nodes
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units

Restrictions (at Baud Rate of 1.5 Mbps)

Cable type Maximum length
per segment
(maximum
length with
Repeater Units)
Branch
line
length
Total
branch line
length per
segment
Branch
location
restrictions
Maximum
number of
nodes per
branch *1
Sub-
branch
line
length
Total sub-
branch line
length per
segment
Maximum
number
of Slave
Units per
segment *2
Round
cable I
Without
branches
100 m (300 m) 0 m *3 0 m *3 32 nodes
With
branches
30 m (90 m) 2.5 m 25 m 3 branches/m 3 nodes 0 m 0 m 32 nodes
Flat Cable I and
Flat Cable II
Round Cable II
30 m (90 m) 2.5 m 25 m 3 branches/m 3 nodes 0.1 m *4 2 m *4 32 nodes
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units
*3. T-branches cannot be connected (only multidrop connections are possible).
*4. T-branch connections from sub-branch lines.

Restrictions (at Baud Rate of 93.75 kbps)

Cable type Maximum length
per segment
(maximum
length with
Repeater Units)
Branch
line
length
Total
branch line
length per
segment
Branch
location
restrictions
Maximum
number of
nodes per
branch *1
Sub-
branch
line
length
Total sub-
branch line
length per
segment
Maximum
number
of Slave
Units per
segment *2
Round cable I 500 m (1500 m) 6 m 120 m 3 branches/m 1 node 32 nodes
Flat Cable I
and Flat Cable II
Round Cable II
No restrictions to a total length per segment of 200 m 32 nodes
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be
connected to one branch line using multidrop or T-branch connections (sub-branches).
*2. Number of nodes including Repeater Units

Specifications

Model CJ1W-CRM21
Applicable Controllers NJ *1 /CJ Series
Unit classification CJ-series Special I/O Unit
Current consumption (Power
supplied from Power Supply
Unit)
400 mA max.at 5 VDC
Communications power supply
connector
One communications power supply connector for Slave Units and Repeater Units on the trunk line
when using Flat Cable *2
Communications power supply
connector allowable current
capacity
5 A max.
Maximum number of mountable
Master Units
One word number assigned:40 Units
Two word numbers assigned:40 Units
Four word numbers assigned:24 Units
Eight word numbers assigned:12 Units
Mounting location According to NJ/CJ-series Special I/O Unit specifications.
Communications power ON/OFF
monitoring
The ON/OFF status of the communications power supply can be detected at the communications
power supply connector.
Data stored in Master Unit
(built-in EEPROM)
1)The following device parameters:
Registration Table
Registration Table Check Type
Registered Slave Unit Participation Monitoring Time,Registered Slave Unit Participation Standby
Mode,and Event Disable Setting
Software Settings Table
Communications Error Communications Stop Mode
Communications Error Input Data Zero Clear Mode
Network settings
2)Part of error history (depends on type of error; mainly serious error related to communications
stopping)
Noise immunity Conforms to IEC 61000-4-4 2 kV (applied to power supply).
Vibration resistance 10 to 61.2 Hz with single-amplitude of 0.1 mm,61.2 to 150 Hz and 14.7 m/s2 in X,Y,and Z
directions for 80 min each (sweep time of 8 min × 10 sweeps =80 min)
Shock resistance 196 m/s2 (3 times each in X,Y,and Z directions)
Dielectric strength 1,000 VAC for 1 min,Leakage current:1 mA max.
Between communications connector or external current supply connector and GR terminal on
Power Supply Unit
Between communications connector or external current supply connector and all Unit connectors
Insulation resistance 20 MΩ min.(between isolated circuits)
Ambient operating temperature 0 to 55°C
Ambient operating humidity 10 to 90%(no condensation)
Ambient operating atmosphere No corrosive gases
Storage temperature 20 to 75°C
Weight 130 g max.(Master Unit only)

*1. Supported only by the CPU Units with unit version 1.01 or later and the Sysmac Studio version 1.02 or higher.
*2. The Master Unit does not required communications power.

(Unit: mm)

CJ1W-CRM21

CJ1W-CRM21 Dimensions 1
Catalog Name
Catalog Number
[size]
Last Update
 CJ1W-CRM21 Data Sheet
[614KB]
Feb 01, 2018

Reviews

There are no reviews yet.

Be the first to review “CJ1W-CRM21”

Your email address will not be published. Required fields are marked *



Exclusive products

Special category of products